Digitus Biometrics db Nexus III Manual de Instalação Página 9

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 20
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 8
Models: db Nexus II, Nexus III Digitus Biometrics, Inc. 2011
Page 9 of 20
Fail Secure Locks (12V)
A fail secure lock needs supplying with a 12V supply to open the lock.
Connect the Ground Lead of the lock to the terminal labeled 0V.
Connect the Live Lead of the lock to the terminal labeled Door Solenoid.
Connect a link between Link and NC and a link between COM and 12V
Fail Safe Locks and Magnetic Locks (24V)
A fail-safe or magnetic lock is permanently supplied with a 24V supply to keep the lock closed. The Digitus
controller does not supply a 24V output. To use a 24V lock a separate power supply will be required. Wire a 24V
Fail Safe lock as shown in the diagram:
Vista de página 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... 19 20

Comentários a estes Manuais

Sem comentários